4–20 mA Scaling Calculator

calculated
calculated
Type in any field to change it. Press × on a value to calculate that field instead.
02468105101520Loop current (mA)Your value

Process value vs Loop current (mA) — other inputs held at your current values.

How to use this calculator

  1. Enter the transmitter’s range — the value at 4 mA (low) and at 20 mA (high), in any engineering unit such as bar, °C, m or m³/h.
  2. Enter the loop current to get the process value and percent of span.

To check a loop the other way round, press × on Loop current and type the process value — the calculator shows the current the transmitter should send. Reverse-acting ranges (for example 100 at 4 mA and 0 at 20 mA) work too.

The formula

% span = (I − 4 mA) ÷ 16 mA
value = low + % span × (high − low)

Worked examples

Pressure transmitter, 0–10 bar, reading 12 mA

  • % span = (12 − 4) ÷ 16 = 50%
  • Value = 0 + 0.5 × 10 = 5 bar

Temperature transmitter, 0–250 °C, reading 16.8 mA

  • % span = (16.8 − 4) ÷ 16 = 80%
  • Value = 0.8 × 250 = 200 °C

Quick reference

Current % of span
4 mA 0%
8 mA 25%
12 mA 50%
16 mA 75%
20 mA 100%

NAMUR NE 43 fault levels

Current Meaning
≤ 3.6 mA Fault (downscale failure)
3.8 – 4.0 mA Under-range, still valid
20.0 – 20.5 mA Over-range, still valid
≥ 21 mA Fault (upscale failure)

Check your transmitter’s manual — some manufacturers use slightly different limits.

Converting mA to volts

Many PLC inputs read the loop as a voltage across a 250 Ω resistor, giving 1–5 V. Use the Ohm’s law calculator to check other resistor values.

Frequently asked questions

How do I convert 4–20 mA to a process value?

Value = low + (mA − 4) ÷ 16 × (high − low). For 12 mA on a 0–10 bar transmitter, (12 − 4) ÷ 16 × 10 = 5 bar.

Why does the signal start at 4 mA instead of 0?

The 4 mA "live zero" powers two-wire transmitters and lets the system tell a real zero reading (4 mA) from a broken wire (0 mA).

What do currents below 4 mA or above 20 mA mean?

Many devices follow NAMUR NE 43. Readings below about 3.6 mA or above about 21 mA signal a fault, such as a sensor failure or open circuit.

Can I calculate the mA output for a given value?

Yes. Press × on Loop current, then type the process value. The calculator gives the expected current, useful for loop checks.