Neutral Current Calculator with Third Harmonics (Neutral Sizing)

In a balanced three-phase circuit the fundamental currents cancel in the neutral, but third harmonics are in phase and add — so a neutral feeding LED lighting, computers or drives can carry more current than the phases. This neutral current calculator finds the neutral current from the third-harmonic content and applies the IEC 60364-5-52 Annex E reduction factors, as explained in neutral conductor sizing with harmonics and power system harmonics.
How to use the neutral current calculator
Enter the phase RMS current and the third-harmonic current as a percentage of the fundamental (the value a power-quality analyser shows in its harmonic spectrum). The calculator splits the phase current into its fundamental and third-harmonic parts, gives the neutral current, re-expresses the harmonic as a percentage of the phase RMS current (the basis IEC 60364-5-52 uses) and returns the design current for choosing a four-core or five-core cable.
Neutral current formulas
I₁ = I ÷ √(1 + h₃²) · I₃ = h₃ × I₁ · IN = 3 × I₃
This assumes balanced phases and that the third harmonic is the only significant triplen harmonic. Other odd harmonics raise the phase RMS slightly but cancel in the neutral.
Worked example
Phase current 100 A with a third harmonic of 30% of the fundamental:
- Fundamental I₁ = 100 ÷ √(1 + 0.3²) = 95.78 A, third harmonic I₃ = 28.73 A
- Neutral current IN = 3 × 28.73 = 86.2 A (0.862 × phase current)
- As a share of the phase RMS current the harmonic is 28.7%, which falls in the 15–33% band
- Size the cable on the phase current with a factor of 0.86: design current = 100 ÷ 0.86 = 116.3 A
Neutral current and design current for 100 A phase current
| 3rd harmonic (% of fundamental) | % of phase current | Neutral current | IN ÷ I | Sized on | Design current |
|---|---|---|---|---|---|
| 10% | 10.0% | 29.9 A | 0.30 | phase | 100.0 A |
| 20% | 19.6% | 58.8 A | 0.59 | phase | 116.3 A |
| 30% | 28.7% | 86.2 A | 0.86 | phase | 116.3 A |
| 40% | 37.1% | 111.4 A | 1.11 | neutral | 129.6 A |
| 50% | 44.7% | 134.2 A | 1.34 | neutral | 156.0 A |
| 60% | 51.4% | 154.3 A | 1.54 | neutral | 154.3 A |
| 80% | 62.5% | 187.4 A | 1.87 | neutral | 187.4 A |
Practical notes
- Do not use a reduced neutral on circuits feeding LED drivers, IT equipment, UPS or single-phase VFDs; many designers use a full-size or double-size neutral for such loads.
- The IEC factors apply to four- and five-core cables where the neutral is inside the same cable and adds heat; for single-core cables, check the neutral on its own current.
- Measure the harmonic spectrum at full load — percentages measured at light load often look high while the actual amps are small.
- Harmonic filters or 3rd-harmonic blocking transformers (zig-zag, delta windings) reduce the neutral current at the source.
Frequently asked questions
Why does the neutral carry third-harmonic current?
The 50 Hz currents of the three phases are 120° apart and cancel in the neutral. Third-harmonic currents of the three phases are all in phase (3 × 120° = 360°), so they add, and the neutral carries three times the third-harmonic current of one phase.
Can the neutral current be higher than the phase current?
Yes. With pure third harmonics the neutral current exceeds the phase current once the third harmonic is about 33% of the phase RMS current (about 35% of the fundamental). Circuits feeding many single-phase rectifier loads commonly reach 1.4–1.7 × phase current.
What are the IEC 60364-5-52 reduction factors for harmonics?
For four- and five-core cables, Annex E gives 1.0 (size on phase current) up to 15% third harmonic, 0.86 (phase current) for 15–33%, 0.86 (neutral current) for 33–45%, and 1.0 (neutral current) above 45%, where the harmonic is a percentage of the phase current.
Do other harmonics add in the neutral?
Only triplen harmonics (3rd, 9th, 15th …) add. The 5th, 7th, 11th and 13th cancel in a balanced system, like the fundamental. Load unbalance adds a further fundamental-frequency neutral current.
Related calculators
- ElectricalTHD CalculatorCalculate total harmonic distortion (THD) of voltage or current from the fundamental and harmonic magnitudes, with IEEE 519 limits.Open calculator
- ElectricalCable Voltage Drop CalculatorCalculate voltage drop in copper or aluminium cable for single-phase and three-phase circuits, and the minimum cable size.Open calculator
- ElectricalkW to Amps CalculatorConvert kilowatts to amps for single-phase, three-phase and DC circuits using voltage and power factor, with charts for 230 V and 415 V.Open calculator
- ElectricalBusbar Size CalculatorEstimate copper or aluminium busbar cross-section and width from current and a design current density, with the resistive loss per metre.Open calculator
- ElectricalCT Burden CalculatorCalculate current transformer (CT) burden in VA from secondary current, lead length, cable size and relay or meter burden, and check it against the CT rating.Open calculator
- ElectricalWire Resistance CalculatorCalculate the resistance of a copper or aluminium wire or cable from length, cross-section and temperature, plus resistance per km.Open calculator