Three-Phase Motor Power & Current Calculator

A motor's nameplate kW is its shaft output, but the supply must also cover losses and reactive current. That is why the current drawn is higher than kW alone suggests. See how to work out motor full-load current (FLC) and how to calculate three-phase power. This free three-phase motor power & current calculator solves for whichever value you leave blank and shows the formula and steps.

calculated
calculated
Type in any field to change it. Press × on a value to calculate that field instead.
0501000204060Rated output (shaft) power (kW)Your value

Line current (A) vs Rated output (shaft) power (kW) — other inputs held at your current values.

How to use the three-phase motor power & current calculator

The defaults show an 11 kW motor on 415 V — the full-load current is calculated. You can also enter a measured current to find the power being drawn. Use the motor’s nameplate values for power factor and efficiency where possible.

For more background, read Motor Efficiency Classes (IEC 60034).

Three-phase motor power & current formulas

Pin = √3 × V × I × cos φ Pout = Pin × η

Worked example

11 kW motor, 415 V, cos φ = 0.85, efficiency 90%:

  • Pin = 11 ÷ 0.90 = 12.22 kW
  • I = 12,222 ÷ (1.732 × 415 × 0.85) = 20.0 A

Approximate full-load currents at 415 V

Motor Current
1.5 kW ~3.3 A
5.5 kW ~11 A
11 kW ~20 A
22 kW ~40 A
45 kW ~80 A

Actual values vary by manufacturer and efficiency class — always check the nameplate.

Current at different voltages

For a 11 kW motor (pf 0.85, efficiency 90%):

Line voltage Full-load current
380 V 21.8 A
400 V 20.8 A
415 V 20.0 A
440 V 18.9 A
480 V 17.3 A
690 V 12.0 A

Single-phase vs three-phase

Single-phase Three-phase
Power formula P = V × I × pf P = √3 × VL × IL × pf
Typical use Homes, small motors under 2–3 kW Industrial motors and large loads
Torque Pulsating Smooth

Starting current

Direct-on-line (DOL) starting draws 6–8 times the full-load current briefly. Star-delta starters reduce it to about one-third, and soft starters or VFDs reduce it further. Size cables, fuses and generators to cope with starting current.

Power factor correction

Motors draw reactive power that does no useful work but loads cables and transformers. Adding capacitors raises power factor towards 0.95–0.98, reducing current and, in many tariffs, electricity charges.

Apparent, real and reactive power

  • Apparent power S (kVA) = √3 × V × I
  • Real power P (kW) = S × pf
  • Reactive power Q (kVAr) = √(S² − P²)

Practical notes

  • Starting current of a direct-on-line motor is typically 6–8× full-load current.
  • Cable sizing must account for both current and length — check with the cable voltage drop calculator.
  • For single-phase, use P = V × I × cos φ instead.

Frequently asked questions

What is the formula for three-phase power?

P = √3 × V × I × cos φ, where V is the line-to-line voltage and I the line current. Shaft power is this multiplied by efficiency.

Why does a motor draw more current than the kW rating suggests?

The kW rating is shaft output. The supply must also cover motor losses (efficiency) and reactive current (power factor), so input current is higher.

What is a typical power factor?

Around 0.80–0.90 at full load for standard induction motors. It drops sharply at light load.

What is the current of a 7.5 kW motor at 415 V?

About 14 A, assuming 0.85 power factor and 88–90% efficiency.

Why is √3 used in three-phase power?

Because line voltage is √3 times phase voltage in a balanced three-phase system.