Pump Affinity Laws Calculator (Speed & Impeller Diameter)

The affinity laws predict how a centrifugal pump's flow, head and power change with speed or impeller diameter: flow scales with the ratio, head with its square and power with its cube. This pump affinity laws calculator applies them for a VFD speed change or an impeller trim — useful when comparing centrifugal vs positive displacement pumps or sizing a VFD.

rpm
1,450 rpm
rpm
1,160 rpm
calculated
calculated
calculated
Type in any field to change it. Press × on a value to calculate that field instead.

How to use the pump affinity laws calculator

Enter the pump’s known duty point — flow, head and shaft power — at the original speed and impeller diameter, then enter the new speed and/or new diameter. Keep D₂ = D₁ for a pure speed change, or N₂ = N₁ for an impeller trim.

Pump affinity laws

Q₂ = Q₁ (N₂/N₁)(D₂/D₁)  ·  H₂ = H₁ (N₂/N₁)²(D₂/D₁)²  ·  P₂ = P₁ (N₂/N₁)³(D₂/D₁)³

Worked example

A pump delivers 100 m³/h at 50 m head and absorbs 18.5 kW at 1,450 rpm. A VFD slows it to 1,160 rpm (ratio 0.80):

  • Q₂ = 100 × 0.80 = 80.0 m³/h
  • H₂ = 50 × 0.80² = 32.0 m
  • P₂ = 18.5 × 0.80³ = 9.47 kW — a 49% power reduction

Speed reduction table (100 m³/h, 50 m, 18.5 kW at 1,450 rpm)

Speed Flow Head Power Power saving
100% (1450 rpm) 100.0 m³/h 50.0 m 18.50 kW 0%
90% (1305 rpm) 90.0 m³/h 40.5 m 13.49 kW 27%
80% (1160 rpm) 80.0 m³/h 32.0 m 9.47 kW 49%
70% (1015 rpm) 70.0 m³/h 24.5 m 6.35 kW 66%
60% (870 rpm) 60.0 m³/h 18.0 m 4.00 kW 78%
50% (725 rpm) 50.0 m³/h 12.5 m 2.31 kW 88%

Notes

  • Efficiency is assumed constant — real savings are slightly lower because motor and VFD losses rise at low load.
  • Check that the reduced head still overcomes the static head of the system.
  • For fans and blowers the same laws apply; see the fan affinity laws calculator.

Frequently asked questions

What are the pump affinity laws?

Q₂/Q₁ = N₂/N₁, H₂/H₁ = (N₂/N₁)² and P₂/P₁ = (N₂/N₁)³. The same relations hold approximately for a change in impeller diameter D at constant speed.

How much energy does slowing a pump save?

Power falls with the cube of speed, so running at 80% speed needs about 51% of the power — a 49% saving — if the system has little static head.

Do the affinity laws work with high static head?

Not directly. They move the pump along curves of constant efficiency, but a system with large static head does not follow those curves — find the new duty point on the system curve instead.

How accurate are they for impeller trimming?

Reasonably for trims up to about 10–15% of diameter. Beyond that efficiency drops and the actual head and flow fall below the predicted values.