Battery Bank Size Calculator (Ah for Backup Time)

Sizing a battery bank starts with the energy the load needs, then allows for inverter losses, how deeply the batteries may be discharged and their loss of capacity with age. This battery bank size calculator gives the amp-hour capacity and the number of batteries in series — see how to calculate battery backup time and the IEEE 485 approach to substation battery sizing.
How to use the battery bank size calculator
Enter the load power, the backup time, the bank voltage, the inverter efficiency, the allowed depth of discharge, a design margin and the voltage of one battery. The calculator returns the energy the load uses, the amp-hour capacity the bank must have and how many batteries to connect in series. Choose the next standard Ah size above the result.
Battery sizing formula
Ah = (P × t) ÷ (Vbank × η × DoD) × k · Nseries = Vbank ÷ Vbattery
Example
A 500 W load must run for 4 hours from a 48 V lead-acid bank through a 90% efficient inverter, discharging to 80% with a 1.25 ageing margin:
- Energy = 500 × 4 = 2,000 Wh
- Ah = 2000 ÷ (48 × 0.9 × 0.8) × 1.25 = 72.3 Ah
- Series batteries = 48 ÷ 12 = 4 → four 12 V, 75 Ah (or larger) batteries
Capacity needed on a 48 V bank
90% inverter efficiency, 80% depth of discharge, 1.25 margin:
| Load | 1 h | 2 h | 4 h | 8 h |
|---|---|---|---|---|
| 250 W | 9 Ah | 18 Ah | 36 Ah | 72 Ah |
| 500 W | 18 Ah | 36 Ah | 72 Ah | 145 Ah |
| 1,000 W | 36 Ah | 72 Ah | 145 Ah | 289 Ah |
| 2,000 W | 72 Ah | 145 Ah | 289 Ah | 579 Ah |
| 3,000 W | 109 Ah | 217 Ah | 434 Ah | 868 Ah |
| 5,000 W | 181 Ah | 362 Ah | 723 Ah | 1,447 Ah |
Practical notes
- Lead-acid batteries last much longer when discharged to only 50%; LiFePO₄ tolerates 80–90% routinely.
- At 0–10 °C, lead-acid capacity falls by 10–20% — add a temperature correction factor.
- The charger must be able to recharge the bank in a reasonable time; see the battery charge time calculator.
- For the UPS kVA rating itself, use the UPS sizing calculator.
Frequently asked questions
How do I calculate battery Ah for backup?
Ah = (load W × hours) ÷ (bank voltage × inverter efficiency × depth of discharge) × margin. A 500 W load for 4 h on a 48 V bank at 90% efficiency, 80% DoD and a 1.25 margin needs about 72 Ah.
How many batteries do I need?
Batteries in series = bank voltage ÷ battery voltage (48 V ÷ 12 V = 4). If one string's Ah is not enough, add parallel strings; total batteries = series × parallel.
Why is the Ah rating at a high discharge rate lower?
Lead-acid capacity is usually quoted at the 10- or 20-hour rate. Discharging in 1–2 hours can deliver only 60–75% of the nameplate Ah, so check the manufacturer's constant-power discharge tables for short backups.
Should I use a higher bank voltage?
For loads above about 1–2 kW, yes. A higher voltage halves the current for the same power, which reduces cable size and losses.
Related calculators
- ElectricalUPS Size CalculatorCalculate the UPS kVA rating needed for your load from watts, power factor and a growth margin, for homes, offices, servers and control panels.Open calculator
- ElectronicsBattery Charging Time CalculatorCalculate how long a battery takes to charge from its capacity, charging current, starting charge level and charging efficiency, lead-acid or lithium.Open calculator
- ElectricalCable Voltage Drop CalculatorCalculate voltage drop in copper or aluminium cable for single-phase and three-phase circuits, and the minimum cable size.Open calculator
- ElectricalAmps to Watts CalculatorConvert amps to watts for DC, single-phase and three-phase circuits, with charts for 12 V, 120 V and 230 V.Open calculator
- Everyday lifeInverter Battery Backup CalculatorFind how many hours your inverter battery will run your load, or the battery Ah you need for a target backup time.Open calculator
- ElectricalSolar String Sizing CalculatorWork out the maximum and minimum number of PV modules per string from Voc, Vmp, temperature coefficients and the inverter's max DC and MPPT voltages.Open calculator