Capacitor Bank kVAr to µF Calculator (3-Phase)

Power factor correction capacitors are rated in kVAr, but the capacitance inside each phase is what you measure and replace. This capacitor bank kVAr calculator converts between kVAr and µF for delta and star banks and gives the line current — see how to calculate capacitor bank kVAr and the guide to capacitor bank sizing for power factor correction.
How to use the capacitor bank kVAr calculator
Enter the bank’s kVAr rating, the line voltage it is connected to, the frequency and whether the capacitors are connected in delta or star. The calculator returns the capacitance needed in each phase, the line current and the reactance of each capacitor. To work out the kVAr of an existing bank, enter the measured µF per phase and clear the kVAr field.
kVAr to µF formulas
Delta: C = Q ÷ (3 × 2πf × VL²) · Star: C = Q ÷ (2πf × VL²)
IL = Q ÷ (√3 × VL) · XC = 1 ÷ (2πf C)
For a single-phase capacitor, C = Q ÷ (2πf × V²) and I = Q ÷ V.
Example
A 50 kVAr delta-connected bank on a 415 V, 50 Hz supply:
- C = 50,000 ÷ (3 × 314.16 × 415²) = 308.0 µF per phase (a star bank would need 924.1 µF)
- I = 50,000 ÷ (1.732 × 415) = 69.6 A
- XC = 1 ÷ (314.16 × 308.0 µF) = 10.33 Ω
Capacitance and current at 415 V, 50 Hz
| Bank rating | µF per phase (delta) | µF per phase (star) | Line current |
|---|---|---|---|
| 5 kVAr | 30.8 µF | 92.4 µF | 7.0 A |
| 10 kVAr | 61.6 µF | 184.8 µF | 13.9 A |
| 25 kVAr | 154.0 µF | 462.1 µF | 34.8 A |
| 50 kVAr | 308.0 µF | 924.1 µF | 69.6 A |
| 75 kVAr | 462.1 µF | 1,386.2 µF | 104.3 A |
| 100 kVAr | 616.1 µF | 1,848.2 µF | 139.1 A |
| 150 kVAr | 924.1 µF | 2,772.3 µF | 208.7 A |
| 200 kVAr | 1,232.1 µF | 3,696.4 µF | 278.2 A |
Output at reduced voltage
Capacitor output varies with V². For a bank rated 50 kVAr at its rated voltage:
| Rated voltage | Supply voltage | Output | Actual kVAr |
|---|---|---|---|
| 415 V | 400 V | 92.9% | 46.5 kVAr |
| 440 V | 415 V | 89.0% | 44.5 kVAr |
| 440 V | 400 V | 82.6% | 41.3 kVAr |
| 480 V | 415 V | 74.8% | 37.4 kVAr |
| 525 V | 415 V | 62.5% | 31.2 kVAr |
| 480 V | 440 V | 84.0% | 42.0 kVAr |
Practical notes
- Size cables and switchgear for about 1.3–1.5 × rated current to allow for harmonics and capacitance tolerance.
- Where the THD is high, use detuned (reactor) banks to avoid resonance.
- Find the kVAr you need from the load and power factors with the power factor correction calculator.
Frequently asked questions
How do I convert kVAr to µF?
For a delta bank, C per phase = Q ÷ (3 × 2πf × V_L²). A 50 kVAr bank at 415 V, 50 Hz needs about 308 µF in each phase. For a star bank, C = Q ÷ (2πf × V_L²), three times larger.
How do I calculate capacitor bank current?
I = Q ÷ (√3 × V_L) for a three-phase bank. 50 kVAr at 415 V draws about 69.6 A per line, whether it is delta or star connected.
What happens if a 440 V capacitor runs at 415 V?
Its output falls with the square of voltage — (415 ÷ 440)² = 89%, so a 50 kVAr unit delivers about 44.5 kVAr. Over-rating the voltage is common to allow for harmonics and overvoltage.
How do I find kVAr from a measured capacitance?
Enter the measured µF per phase and clear the kVAr field. A drop of more than about 5–10% from nameplate usually means the capacitor should be replaced.
Related calculators
- ElectricalPower Factor Correction CalculatorCalculate the capacitor bank kVAr and capacitance needed to raise power factor from its present value to a target, with current reduction.Open calculator
- ElectricalkVA to kW ConverterConvert kVA to kW and kW to kVA using power factor, for generators, UPS, transformers and DG set sizing.Open calculator
- ElectronicsReactance and Impedance CalculatorCalculate inductive reactance, capacitive reactance and series RLC impedance at any frequency, with phase angle.Open calculator
- ElectricalTHD CalculatorCalculate total harmonic distortion (THD) of voltage or current from the fundamental and harmonic magnitudes, with IEEE 519 limits.Open calculator
- ElectricalThree-Phase Motor Power & Current CalculatorCalculate input power, output power and full-load current of a three-phase motor from voltage, power factor and efficiency.Open calculator
- ElectricalkW to Amps CalculatorConvert kilowatts to amps for single-phase, three-phase and DC circuits using voltage and power factor, with charts for 230 V and 415 V.Open calculator