Autotransformer Calculator (Currents, kVA & Copper Saving)

An autotransformer uses a single tapped winding, so part of the power passes straight through by conduction and only the rest is transformed magnetically. This autotransformer calculator gives the line and common-winding currents and the split between transformed and conducted kVA — see the autotransformer working principle for how the shared winding works.
How to use the autotransformer calculator
Enter the load rating in kVA and the high- and low-voltage sides of the autotransformer (it works the same for step-up and step-down). The calculator returns the current on each side, the current in the common section of the winding, how much of the power is transformed magnetically versus conducted directly, and the copper saved compared with a two-winding transformer of the same rating.
Autotransformer formulas
IH = S ÷ VH · IL = S ÷ VL · Icommon = IL − IH
Stransformed = S (1 − K) · Sconducted = S K · K = VL ÷ VH
Example
A 10 kVA, 240 V to 200 V step-down autotransformer:
- IH = 10,000 ÷ 240 = 41.67 A, IL = 10,000 ÷ 200 = 50.00 A
- Common winding current = 50 − 41.67 = 8.33 A
- Transformed = 10 × (1 − 200/240) = 1.667 kVA; conducted = 8.333 kVA
- Copper saved ≈ 83.3% of a 10 kVA two-winding transformer
Transformed power and copper saving by voltage ratio
| Ratio | K | Share of kVA transformed | Copper saving |
|---|---|---|---|
| 240 / 220 V | 0.917 | 8.3% | 91.7% |
| 240 / 200 V | 0.833 | 16.7% | 83.3% |
| 415 / 380 V | 0.916 | 8.4% | 91.6% |
| 480 / 415 V | 0.865 | 13.5% | 86.5% |
| 400 / 230 V | 0.575 | 42.5% | 57.5% |
| 240 / 120 V | 0.500 | 50.0% | 50.0% |
| 400 / 100 V | 0.250 | 75.0% | 25.0% |
Where autotransformers are used
- Motor starting: autotransformer starters apply 50–80% voltage taps, cutting line current to K² of the direct-on-line value.
- Grid interconnection: large 400/220 kV and 220/132 kV interbus transformers, where the ratio is close to 1.
- Variacs: variable autotransformers for test benches.
- Not suitable where isolation is required, or for large ratios such as 11 kV/415 V.
Frequently asked questions
How do you calculate autotransformer current?
I_high = S ÷ V_high and I_low = S ÷ V_low, as for any transformer. The common part of the winding carries only the difference, I_low − I_high.
How much power is transformed in an autotransformer?
Only S × (1 − V_low ÷ V_high). The rest, S × V_low ÷ V_high, is conducted straight through the shared winding. A 240/200 V, 10 kVA unit transforms just 1.67 kVA.
How much copper does an autotransformer save?
Copper needed = (1 − K) × that of a two-winding transformer, with K = V_low ÷ V_high, so the saving is K. The closer the two voltages, the bigger the saving.
What is the main disadvantage of an autotransformer?
There is no electrical isolation between primary and secondary, and if the common winding opens, the full input voltage can appear at the output. It also has lower impedance, so fault currents are higher.
Related calculators
- ElectricalTransformer Turns Ratio CalculatorCalculate transformer secondary voltage, turns ratio and primary or secondary current from the number of turns or voltages.Open calculator
- ElectricalTransformer Current CalculatorCalculate primary and secondary full-load current of single-phase and three-phase transformers from kVA and voltages.Open calculator
- ElectricalTransformer Size CalculatorCalculate the transformer kVA rating needed for your connected load from kW, power factor, diversity factor and future growth, and pick the next standard size.Open calculator
- ElectricalTransformer Efficiency CalculatorCalculate transformer efficiency at any load and power factor from no-load (core) and full-load (copper) losses, plus the load for maximum efficiency.Open calculator
- ElectricalMotor Starting Voltage Dip CalculatorEstimate the voltage dip when a motor starts on a transformer, from motor kW, starting current, transformer kVA and Z%, for DOL, star-delta and soft starts.Open calculator
- ElectricalCT Burden CalculatorCalculate current transformer (CT) burden in VA from secondary current, lead length, cable size and relay or meter burden, and check it against the CT rating.Open calculator