Motor Starting Voltage Dip Calculator (Transformer kVA & Z%): formula and free online calculator

When an induction motor starts it draws five to seven times its full-load current at a low power factor, and that current through the supply impedance pulls the bus voltage down. This motor starting voltage dip calculator estimates the dip from the motor's starting kVA and the transformer's short-circuit kVA, using the simplified method in motor starting voltage dip calculation, and compares the motor starting methods.

kVA
1,000 kVA
kVA
calculated16,666.67 kVA
kVA
calculated
calculated
Small — fine for most loads
calculated
Type in any field to change it. Press × on a value to calculate that field instead.

How to use the motor starting voltage dip calculator

Enter the transformer kVA and impedance, the motor output, efficiency, power factor and the starting current as a multiple of full-load current. The calculator returns the transformer short-circuit capacity, the motor starting kVA and the voltage dip on the transformer secondary. Change the starting-current multiple to compare starting methods.

Motor starting voltage dip formula

Ssc = ST ÷ Z%  ·  Sstart = k × P ÷ (η × PF)

ΔV = Sstart ÷ (Ssc + Sstart)

This is the impedance-divider method: the motor’s locked-rotor impedance and the supply impedance form a voltage divider. It assumes an infinite upstream grid; add the utility fault level for weak supplies.

Worked example

A 110 kW motor (η = 95%, PF = 0.87) started direct-on-line at 6 × FLC on a 1,000 kVA, 6% transformer:

  • Short-circuit capacity Ssc = 1,000 ÷ 0.06 = 16,667 kVA
  • Starting kVA = 6 × 110 ÷ (0.95 × 0.87) = 799 kVA
  • Voltage dip = 799 ÷ (16,667 + 799) = 4.57%, leaving 95.4% voltage during the start

Effect of starting method (same motor and transformer)

Starting method Line current Starting kVA Voltage dip
Direct-on-line (DOL) 6.00 × FLC 799 kVA 4.57%
Autotransformer, 80% tap 3.84 × FLC 511 kVA 2.98%
Soft starter (≈3.5 × FLC) 3.50 × FLC 466 kVA 2.72%
Star–delta 2.00 × FLC 266 kVA 1.57%
VFD (≈1.2 × FLC) 1.20 × FLC 160 kVA 0.95%

DOL voltage dip by motor and transformer size

Motor 500 kVA (4.5%) 1,000 kVA (6%) 2,000 kVA (6%)
37 kW 2.4% 1.6% 0.8%
75 kW 4.7% 3.2% 1.6%
110 kW 6.7% 4.6% 2.3%
160 kW 9.5% 6.5% 3.4%
250 kW 14.0% 9.8% 5.2%

Assumes η = 95%, PF = 0.87 and 6 × FLC starting current.

Practical notes

  • The motor’s torque falls with the square of voltage: a 15% dip leaves only about 72% of the rated starting torque.
  • Long cables add impedance between the transformer and the motor; the dip at the motor terminals is then larger than the bus dip shown here.
  • On generator supplies the dip is much larger because a generator’s transient reactance (typically 15–30%) is far higher than a transformer’s impedance.

Frequently asked questions

How do you calculate the voltage dip when a motor starts?

A simple estimate is ΔV = S_start ÷ (S_sc + S_start), where S_start is the motor's starting kVA (starting current multiple × rated kVA) and S_sc the short-circuit kVA of the supply (transformer kVA ÷ Z%).

What voltage dip is acceptable during motor starting?

Common design limits are around 10–15% at the motor terminals so the motor still develops enough torque and contactors do not drop out, and lower — about 3–5% — at buses feeding lighting or sensitive electronics, where flicker is noticed.

Why is the result conservative?

The formula adds impedance magnitudes as if they were in phase. In reality the motor's starting power factor (0.2–0.4) and the transformer's X/R ratio differ slightly, so the true dip is usually a little smaller. Upstream source impedance and cable impedance make it larger, so include them for long feeders.

How do I reduce motor starting voltage dip?

Use star–delta, autotransformer or soft starting, or a VFD; start large motors one at a time; or supply them from a larger or lower-impedance transformer.

Free widget

Put this calculator on your website

Copy one snippet. It resizes itself and works on any site or blog.

<iframe src="https://zentacalculator.com/embed/electrical/motor-starting-voltage-dip/" title="Motor Starting Voltage Dip Calculator (Transformer kVA & Z%)" width="100%" height="640" style="border:1px solid #e2e5ee;border-radius:12px;max-width:720px" loading="lazy"></iframe>
<p style="font-size:13px"><a href="https://zentacalculator.com/electrical/motor-starting-voltage-dip/">Motor Starting Voltage Dip Calculator (Transformer kVA & Z%)</a> by <a href="https://zentacalculator.com/">Zenta Calculator</a></p>
<script>addEventListener('message',function(e){if(e.origin==='https://zentacalculator.com'&&e.data&&e.data.zentaHeight){document.querySelectorAll('iframe[src="https://zentacalculator.com/embed/electrical/motor-starting-voltage-dip/"]').forEach(function(f){if(f.contentWindow===e.source)f.style.height=e.data.zentaHeight+'px'})}})</script>
Why Zenta Calculator

From formula to answer in seconds

One clear path from the numbers you have to a result you can use, for students, engineers and everyday users.

  1. 01

    Enter what you know

    Type any values you have, in the units you use. Leave the unknown blank and the calculator solves for it.

  2. 02

    See the formula and steps

    Every result shows the equation, a worked example and a chart, so you understand the answer and not just the number.

  3. 03

    Get answers you can trust

    Formulas follow published standards and textbooks, and every worked example is checked before a page goes live.