Cooling Tower Calculator (Range, Approach, Evaporation): formula and free online calculator

A cooling tower removes heat from condenser or process water by evaporating a small part of it into a moving air stream. This cooling tower calculator finds the range, approach and effectiveness, the heat rejected, and the evaporation, drift, blowdown and makeup flows.

Utility engineers and HVAC operators use it to check tower performance against design, plan makeup water supply and set the blowdown that keeps dissolved solids under control.

calculated
calculated
calculated
calculated
calculated
calculated
calculated
calculated
Type in any field to change it. Press × on a value to calculate that field instead.

How to use the cooling tower calculator

Enter the hot water temperature returning to the tower, the cold water temperature leaving the basin, the ambient wet bulb temperature, the circulating water flow, the cycles of concentration and the drift loss. The calculator gives the range, the approach, the tower effectiveness, the heat rejected (in kW or refrigeration tons) and the evaporation, drift, blowdown and makeup flows. Leave any one input blank to solve for it — for example enter the makeup you can afford and find the cycles of concentration you must reach.

Cooling tower formulas

Range = Thot − Tcold  ·  Approach = Tcold − Twb  ·  Effectiveness = Range ÷ (Range + Approach)

Heat rejected = ρ cp Q × Range  ·  E = 0.00153 × Q × Range(°C)  ·  B = E ÷ (COC − 1) − D  ·  M = E + B + D

Water is taken as 1,000 kg/m³ with cp = 4.186 kJ/kg·K. E is evaporation, D drift, B blowdown and M makeup, all in the same flow units as Q.

Worked example

A 500 m³/h condenser water circuit returns at 37 °C and leaves the tower at 32 °C on a day with a 28 °C wet bulb; the tower runs at 4 cycles with 0.02% drift:

  • Range = 37 − 32 = 5 °C; approach = 32 − 28 = 4 °C
  • Effectiveness = 5 ÷ (5 + 4) = 55.6%
  • Heat rejected = 1,000 × 4.186 × 500 ÷ 3,600 × 5 = 2,907 kW (827 TR)
  • Evaporation E = 0.00153 × 500 × 5 = 3.825 m³/h
  • Drift D = 0.02% × 500 = 0.10 m³/h
  • Blowdown B = 3.825 ÷ (4 − 1) − 0.10 = 1.175 m³/h
  • Makeup M = 3.825 + 1.175 + 0.10 = 5.10 m³/h (about 122 m³ per day)

Evaporation loss by range and flow

Range 100 m³/h 500 m³/h 1,000 m³/h 5,000 m³/h % of flow
3 °C (5.4 °F) 0.46 m³/h 2.29 m³/h 4.59 m³/h 22.95 m³/h 0.46%
4 °C (7.2 °F) 0.61 m³/h 3.06 m³/h 6.12 m³/h 30.60 m³/h 0.61%
5 °C (9 °F) 0.77 m³/h 3.82 m³/h 7.65 m³/h 38.25 m³/h 0.77%
6 °C (10.8 °F) 0.92 m³/h 4.59 m³/h 9.18 m³/h 45.90 m³/h 0.92%
8 °C (14.4 °F) 1.22 m³/h 6.12 m³/h 12.24 m³/h 61.20 m³/h 1.22%
10 °C (18 °F) 1.53 m³/h 7.65 m³/h 15.30 m³/h 76.50 m³/h 1.53%
12 °C (21.6 °F) 1.84 m³/h 9.18 m³/h 18.36 m³/h 91.80 m³/h 1.84%

Blowdown and makeup by cycles of concentration

Per 1,000 m³/h of circulating water with a 5 °C range (evaporation 7.65 m³/h), drift neglected:

Cycles (COC) Evaporation (m³/h) Blowdown (m³/h) Makeup (m³/h) Makeup per day
1.5 7.65 15.30 22.95 551 m³
2 7.65 7.65 15.30 367 m³
3 7.65 3.82 11.47 275 m³
4 7.65 2.55 10.20 245 m³
5 7.65 1.91 9.56 229 m³
6 7.65 1.53 9.18 220 m³
8 7.65 1.09 8.74 210 m³
10 7.65 0.85 8.50 204 m³

Practical notes

  • Approach sets the tower size: halving the approach roughly doubles the fill and air required, so designs rarely go below 3 °C (5 °F). A rising approach at the same load and wet bulb points to fouled fill, blocked nozzles or a fan problem.
  • Range follows the load: for a fixed flow the range rises and falls with the heat load; the approach stays fairly constant.
  • Cycles of concentration are usually measured as the ratio of conductivity or chloride in the basin to that in the makeup water. Gains above about 6–8 cycles are small, while scaling risk keeps rising.
  • Design wet bulb: size the tower on the local summer design wet bulb (often the 1% or 0.4% value), not the dry bulb temperature. Use the dew point calculator for humidity checks and the chiller tonnage calculator to size the chiller the tower serves.

Finding the cycles from conductivity readings

Cycles of concentration are rarely known directly; they are read from conductivity. If the makeup water measures 250 µS/cm and the basin 1200 µS/cm, the tower runs at 1200 ÷ 250 = 4.8 cycles. Entered with the other default values, that gives:

  • Blowdown = 3.825 ÷ (4.8 − 1) − 0.10 = 0.907 m³/h
  • Makeup = 4.832 m³/h, against 5.10 m³/h at 4 cycles

Pushing on to 6 cycles cuts the makeup to 4.59 m³/h, a saving of about 12 m³ a day. Whether that is safe depends on the makeup water’s hardness, alkalinity and silica, which set the scaling limit for the treatment programme.

Checking a tower against its design

A tower test needs four readings taken together at steady load: hot water temperature at the inlet header, cold water temperature at the basin outlet, wet bulb temperature at the air inlet (an aspirated psychrometer, not a dry bulb sensor) and circulating flow. Flow is often checked with a clamp-on meter on the riser; see how an ultrasonic flow meter works for its limits on lined or corroded pipe.

On a humid day with a 30 °C wet bulb, a tower holding the same 4 K approach delivers 34 °C water, and with a 5 to 34 °C duty it still rejects 2,907 kW. The chiller now sees condenser water 2 K warmer, which typically costs it a few percent more compressor power per kelvin. A tower that drifts from a 4 K to a 6 K approach at the same wet bulb and load needs its fill, nozzles and fan checked.

Common mistakes

  • Using the dry bulb temperature. Evaporative cooling is limited by the wet bulb; using the dry bulb makes the approach look far better than it is.
  • Reading cold water temperature in the basin surface. Measure in the outlet pipe or at the pump suction, where the water is mixed.
  • Treating effectiveness as the main performance figure. Effectiveness changes with range; the approach at a known wet bulb, load and flow is what tower suppliers guarantee.
  • Counting drift as blowdown. Drift does remove dissolved solids, but modern eliminators keep it so small that it cannot replace controlled blowdown.
  • Setting blowdown by a fixed timer. Load and weather change the evaporation through the day; conductivity controlled blowdown holds the cycles steady.

Frequently asked questions

What are range and approach in a cooling tower?

The range is the drop in water temperature across the tower (hot water in minus cold water out); it is set by the heat load and the flow. The approach is how close the cold water gets to the ambient wet bulb temperature (cold water minus wet bulb); it depends on the tower size and fill. A tower cooling water from 37 °C to 32 °C at a 28 °C wet bulb has a 5 °C range and a 4 °C approach.

How do you calculate cooling tower efficiency?

Effectiveness = range ÷ (range + approach) = (T_hot − T_cold) ÷ (T_hot − T_wet bulb). It is the fraction of the maximum possible cooling actually achieved — 5 ÷ (5 + 4) = 55.6% in the example. Typical towers run at 55–75%; the water can never be cooled below the wet bulb temperature.

How much water does a cooling tower evaporate?

About 0.153% of the circulating flow for every 1 °C of range (the rule E = 0.00085 × flow × range in °F from Perry's handbook), so roughly 1% of the flow for every 6.5 °C (12 °F). A 500 m³/h tower with a 5 °C range evaporates about 3.8 m³/h. The rule assumes nearly all heat leaves as latent heat; the real figure is a little lower in cold weather.

How do you calculate blowdown and makeup water?

Blowdown B = E ÷ (COC − 1) − drift, and makeup M = evaporation + blowdown + drift = E × COC ÷ (COC − 1). Raising the cycles of concentration from 2 to 5 cuts the makeup by over a third, but the water treatment must then cope with higher scaling and corrosion potential.

How do I find cycles of concentration from conductivity?

Divide the basin water conductivity by the makeup water conductivity. 1200 µS/cm in the basin with 250 µS/cm makeup is 4.8 cycles. Chloride or silica ratios give the same figure and are not upset by acid dosing.

What happens to the cold water temperature on a more humid day?

It rises with the wet bulb. A tower that holds a 4 K approach gives 32 °C water at a 28 °C wet bulb but about 34 °C at a 30 °C wet bulb, for the same load and flow.

Free widget

Put this calculator on your website

Copy one snippet. It resizes itself and works on any site or blog.

<iframe src="https://zentacalculator.com/embed/engineering/cooling-tower/" title="Cooling Tower Calculator (Range, Approach, Evaporation)" width="100%" height="640" style="border:1px solid #e2e5ee;border-radius:12px;max-width:720px" loading="lazy"></iframe>
<p style="font-size:13px"><a href="https://zentacalculator.com/engineering/cooling-tower/">Cooling Tower Calculator (Range, Approach, Evaporation)</a> by <a href="https://zentacalculator.com/">Zenta Calculator</a></p>
<script>addEventListener('message',function(e){if(e.origin==='https://zentacalculator.com'&&e.data&&e.data.zentaHeight){document.querySelectorAll('iframe[src="https://zentacalculator.com/embed/engineering/cooling-tower/"]').forEach(function(f){if(f.contentWindow===e.source)f.style.height=e.data.zentaHeight+'px'})}})</script>
Why Zenta Calculator

From formula to answer in seconds

One clear path from the numbers you have to a result you can use, for students, engineers and everyday users.

  1. 01

    Enter what you know

    Type any values you have, in the units you use. Leave the unknown blank and the calculator solves for it.

  2. 02

    See the formula and steps

    Every result shows the equation, a worked example and a chart, so you understand the answer and not just the number.

  3. 03

    Get answers you can trust

    Formulas follow published standards and textbooks, and every worked example is checked before a page goes live.