Hazen–Williams Calculator (Water Pipe Head Loss)
The Hazen–Williams equation is the go-to empirical formula for friction loss in water supply, fire-protection and irrigation pipes, using a single roughness C factor. This Hazen–Williams calculator gives head loss, pressure drop and velocity in SI units — see how to calculate pressure drop in pipes.
How to use the Hazen–Williams calculator
Enter the flow rate, the pipe internal diameter, its length and the C factor for the pipe material. You get the friction head loss, the equivalent pressure drop for water and the flow velocity. Add fittings with the minor losses calculator.
Hazen–Williams equation (SI)
hf = 10.67 × L × Q1.852 ÷ (C1.852 × d4.87)
Δp = ρ g hf ≈ 9.81 kPa per metre of head
Example
50 m³/h of water through 100 m of 100 mm pipe, C = 130:
- Q = 50 ÷ 3600 = 0.01389 m³/s
- hf = 3.498 m of head
- Δp = 34.30 kPa (4.97 psi)
- Velocity = 1.77 m/s
Head loss per 100 m at 50 m³/h (C = 130)
| Pipe ID | Velocity | Head loss | Pressure drop |
|---|---|---|---|
| 65 mm | 4.19 m/s | 28.507 m | 279.56 kPa |
| 80 mm | 2.76 m/s | 10.369 m | 101.69 kPa |
| 100 mm | 1.77 m/s | 3.498 m | 34.30 kPa |
| 125 mm | 1.13 m/s | 1.180 m | 11.57 kPa |
| 150 mm | 0.79 m/s | 0.485 m | 4.76 kPa |
| 200 mm | 0.44 m/s | 0.120 m | 1.17 kPa |
Typical C factors
| Pipe material | C |
|---|---|
| PVC, HDPE, copper (smooth) | 140–150 |
| Cement-lined ductile iron | 130–140 |
| New welded steel | 120 |
| Galvanised steel | 120 |
| Old cast iron | 80–100 |
Frequently asked questions
What is the Hazen–Williams formula in SI units?
h_f = 10.67 × L × Q^1.852 ÷ (C^1.852 × d^4.87), with head loss and length in metres, flow in m³/s and diameter in metres.
When should I not use Hazen–Williams?
It is valid only for water at roughly 5–25 °C in turbulent flow. For other liquids, hot water, viscous fluids or gases, use the Darcy–Weisbach equation.
What C factor should I use?
About 150 for plastic pipe, 130–140 for copper and new lined pipe, 120 for new steel and 100 or less for old, tuberculated cast iron. Design codes often specify the value.
How does pipe size affect head loss?
Strongly — head loss varies with d^−4.87, so one size larger pipe often cuts friction loss by more than half.