Ultrasonic Level Calculator (Time of Flight and Temperature)

An ultrasonic level transmitter sends a sound pulse down to the liquid surface and times the echo. Because the speed of sound in air changes about 0.6 m/s per °C, temperature compensation is essential. This ultrasonic level calculator converts echo time into distance and level — see ultrasonic level transmitter working and how an ultrasonic level transmitter works.

°C
calculated
calculated
calculated
Type in any field to change it. Press × on a value to calculate that field instead.

How to use the ultrasonic level calculator

Enter the round-trip echo time, the air temperature in the tank and the empty distance from the sensor face to the bottom (0% level). You get the speed of sound, the distance to the surface and the liquid level.

Ultrasonic level formula

c = 331.3 × √(1 + T/273.15) m/s  ·  d = c × t ÷ 2  ·  Level = E − d

Speed of sound in air

Temperature Speed of sound Distance error if 20 °C assumed
-20 °C 318.9 m/s -7.1%
0 °C 331.3 m/s -3.5%
10 °C 337.3 m/s -1.7%
20 °C 343.2 m/s +0.0%
30 °C 349.0 m/s +1.7%
40 °C 354.7 m/s +3.4%
60 °C 365.9 m/s +6.6%
80 °C 376.7 m/s +9.8%

Example

Echo time 20 ms at 30 °C, empty distance 6 m:

  • c = 349.0 m/s, distance = 349.0 × 0.020 ÷ 2 = 3.49 m
  • Level = 6 − 3.49 = 2.51 m

Installation tips

  • Keep the liquid surface out of the blanking distance at maximum level.
  • Mount away from the tank wall, inlet stream and internal ladders to avoid false echoes.
  • Use the sensor’s built-in temperature probe; vapour layers with a different gas composition still cause errors.
  • For foam, vapour or pressure, consider radar level measurement.

Frequently asked questions

How does an ultrasonic level sensor calculate distance?

Distance = speed of sound × echo time ÷ 2, because the pulse travels down and back. Level = empty distance − measured distance.

How much does temperature affect the reading?

The speed of sound changes by about 0.17% per °C. Without compensation, a 20 °C error causes about 3.5% distance error.

What is the blanking distance?

A zone just below the sensor where echoes cannot be measured while the transducer is still ringing — typically 0.25–0.5 m.

When is ultrasonic a poor choice?

With heavy vapour, foam, dust, high pressure or vacuum, or strong turbulence. Radar is usually better in those cases.