Polarization Index Calculator (PI & DAR Insulation Test)

A healthy insulation's resistance keeps rising during a megger test as the dielectric polarizes, while moist or contaminated insulation levels off quickly. This polarization index calculator turns the 30-second, 1-minute and 10-minute readings into the PI and DAR — follow the insulation resistance test with a megger procedure and compare with motor insulation classes.
How to use the polarization index calculator
Apply the test voltage with an insulation resistance tester and record the readings at 30 seconds, 1 minute and 10 minutes. Enter them and the calculator returns the polarization index and the dielectric absorption ratio, each with a condition rating.
Polarization index formulas
PI = R10 min ÷ R1 min · DAR = R60 s ÷ R30 s
Worked example
Motor winding readings at 1,000 V DC: 800 MΩ at 30 s, 1,000 MΩ at 1 min, 2,500 MΩ at 10 min:
- PI = 2,500 ÷ 1,000 = 2.50 — good (above the IEEE 43 minimum of 2.0)
- DAR = 1,000 ÷ 800 = 1.25 — questionable on its own, which is why the 10-minute test is preferred
Interpreting PI and DAR
| Condition | PI | DAR |
|---|---|---|
| Dangerous / poor | below 1.0 | below 1.0 |
| Questionable | 1.0 – 2.0 | 1.0 – 1.25 |
| Good | 2.0 – 4.0 | 1.25 – 1.6 |
| Very good | above 4.0 | above 1.6 |
Notes
- Insulation resistance roughly halves for every 10 °C rise — correct readings to 40 °C before comparing with past tests; PI is a ratio and is less sensitive to temperature.
- Discharge the winding fully after the test, for at least four times the test duration.
Frequently asked questions
How is the polarization index calculated?
PI = insulation resistance after 10 minutes ÷ insulation resistance after 1 minute, both at the same test voltage. 2,500 MΩ ÷ 1,000 MΩ gives a PI of 2.5.
What is a good polarization index?
IEEE 43 recommends a minimum PI of 2.0 for class B, F and H insulation and 1.5 for class A. Below 1.0 the insulation is likely wet, dirty or damaged.
What is the dielectric absorption ratio?
DAR = 60-second reading ÷ 30-second reading. It is a quicker test; above about 1.25 is acceptable and above 1.6 excellent.
When is the PI test not meaningful?
If the 1-minute insulation resistance is above about 5,000 MΩ, IEEE 43 notes the PI may not be meaningful because the current is too small to measure reliably.
Related calculators
- ElectricalThree-Phase Motor Power & Current CalculatorCalculate input power, output power and full-load current of a three-phase motor from voltage, power factor and efficiency.Open calculator
- ElectricalEarthing Resistance CalculatorCalculate the earth resistance of a vertical earth rod or pipe electrode from soil resistivity, length and diameter, and how many rods you need.Open calculator
- ElectricalWire Resistance CalculatorCalculate the resistance of a copper or aluminium wire or cable from length, cross-section and temperature, plus resistance per km.Open calculator
- ElectricalTransformer Efficiency CalculatorCalculate transformer efficiency at any load and power factor from no-load (core) and full-load (copper) losses, plus the load for maximum efficiency.Open calculator
- ElectricalTHD CalculatorCalculate total harmonic distortion (THD) of voltage or current from the fundamental and harmonic magnitudes, with IEEE 519 limits.Open calculator
- ElectricalVoltage Unbalance CalculatorCalculate percentage voltage unbalance from three line voltages, plus the motor derating and extra temperature rise it causes.Open calculator