PFDavg Calculator (SIL Verification, 1oo1)

In a safety instrumented system, each safety function must reach a target probability of failure on demand (PFDavg) that sets its SIL. For a single channel, PFDavg depends on the dangerous undetected failure rate and how often it is proof tested. This PFDavg calculator does the 1oo1 calculation — see the PFDavg calculation formula, what SIL is and SIL verification.

FIT
years
calculated
calculated
calculated
Type in any field to change it. Press × on a value to calculate that field instead.

How to use the PFDavg calculator

Enter the dangerous undetected failure rate λDU for the whole safety function (sensor + logic solver + final element) in FIT, and the proof test interval in years. You get PFDavg, the risk reduction factor and the SIL band that PFDavg alone supports.

PFDavg formula (1oo1, low demand)

PFDavg ≈ λDU × TI ÷ 2  ·  RRF = 1 ÷ PFDavg

This simplified formula assumes perfect proof testing and ignores repair time and common-cause failures.

SIL bands (low-demand mode)

SIL PFDavg Risk reduction factor
SIL 1 ≥ 10⁻² to < 10⁻¹ 10 – 100
SIL 2 ≥ 10⁻³ to < 10⁻² 100 – 1,000
SIL 3 ≥ 10⁻⁴ to < 10⁻³ 1,000 – 10,000
SIL 4 ≥ 10⁻⁵ to < 10⁻⁴ 10,000 – 100,000

PFDavg vs proof test interval (λDU = 500 FIT)

Test interval PFDavg RRF
3 months 5.48e-04 1,826
6 months 1.10e-03 913
1 year 2.19e-03 457
2 years 4.38e-03 228
5 years 1.09e-02 91

Redundant architectures

Architecture Simplified PFDavg
1oo1 λDU TI / 2
1oo2 (λDU TI)² / 3 + β λDU TI / 2
2oo3 (λDU TI)² + β λDU TI / 2

β is the common-cause factor (typically 2–10%). For a full assessment, follow IEC 61508/61511 — see SIL determination methods.

Frequently asked questions

What is the PFDavg formula for 1oo1?

PFDavg ≈ λDU × TI ÷ 2, where λDU is the dangerous undetected failure rate per hour and TI the proof test interval in hours.

What PFDavg does each SIL need?

SIL 1 — 10⁻² to 10⁻¹; SIL 2 — 10⁻³ to 10⁻²; SIL 3 — 10⁻⁴ to 10⁻³; SIL 4 — 10⁻⁵ to 10⁻⁴ (low-demand mode, IEC 61511).

Is PFDavg enough to claim a SIL?

No. You must also meet architectural constraints (hardware fault tolerance), systematic capability and proof-test coverage requirements.

How do I lower PFDavg?

Test more often, choose devices with lower λDU, add redundancy (1oo2, 2oo3) or improve diagnostic coverage.