5-Point Calibration Calculator (0–25–50–75–100% Table)

A 5-point check at 0, 25, 50, 75 and 100% of range is the standard way to calibrate a transmitter and reveal zero, span and linearity errors. This 5-point calibration calculator builds the table of input values and expected outputs for any range — see the calibration process for a DP transmitter.

calculated
calculated
calculated
calculated
calculated
calculated
Type in any field to change it. Press × on a value to calculate that field instead.

How to use the 5-point calibration calculator

Enter the calibrated input range (LRV and URV) and the output range (4 and 20 for a 4–20 mA transmitter, 1 and 5 for a 1–5 V signal). The calculator gives the input to apply and the output you should read at 25, 50 and 75%; the 0% and 100% points are the range ends you entered. Record the measured values and check each one with the calibration error calculator.

Calibration point formula

Inputp = LRV + p × (URV − LRV)  ·  Outputp = Olow + p × (Ohigh − Olow)

where p = 0, 0.25, 0.5, 0.75 and 1.

Example: 0–10 bar pressure transmitter

Point Input 4–20 mA output 1–5 V output
0% 0 bar 4.00 mA 1.00 V
25% 2.5 bar 8.00 mA 2.00 V
50% 5 bar 12.00 mA 3.00 V
75% 7.5 bar 16.00 mA 4.00 V
100% 10 bar 20.00 mA 5.00 V

Calibration procedure

  1. Isolate the transmitter, connect the pressure source and a reference gauge, and connect a multimeter or calibrator in the loop.
  2. Apply each point upscale (0 → 100%) and record the output, then repeat downscale (100 → 0%).
  3. Calculate the error at each point as % of span. If any point is out of tolerance, adjust zero and span and repeat to record as-left data.
  4. For DP flow transmitters with square-root extraction, the output at 25% DP is 50% flow — see the DP flow square-root calculator.

Frequently asked questions

Why calibrate at five points?

Zero and span alone only fix the ends of the range. The 25, 50 and 75% points show non-linearity, and testing upscale then downscale reveals hysteresis.

What are the 5 calibration points for a 4–20 mA transmitter?

4, 8, 12, 16 and 20 mA, corresponding to 0, 25, 50, 75 and 100% of the calibrated input range.

Does the table work for a suppressed or elevated zero?

Yes. Enter a negative LRV for an elevated range (for example −50 to +150 mbar) and the input points are spaced across that range.

What about reverse-acting outputs?

Enter the output high value as the low and vice versa (for example 20 and 4) — the expected outputs then decrease as the input rises.