5-Point Calibration Calculator (0–25–50–75–100% Table)
A 5-point check at 0, 25, 50, 75 and 100% of range is the standard way to calibrate a transmitter and reveal zero, span and linearity errors. This 5-point calibration calculator builds the table of input values and expected outputs for any range — see the calibration process for a DP transmitter.
How to use the 5-point calibration calculator
Enter the calibrated input range (LRV and URV) and the output range (4 and 20 for a 4–20 mA transmitter, 1 and 5 for a 1–5 V signal). The calculator gives the input to apply and the output you should read at 25, 50 and 75%; the 0% and 100% points are the range ends you entered. Record the measured values and check each one with the calibration error calculator.
Calibration point formula
Inputp = LRV + p × (URV − LRV) · Outputp = Olow + p × (Ohigh − Olow)
where p = 0, 0.25, 0.5, 0.75 and 1.
Example: 0–10 bar pressure transmitter
| Point | Input | 4–20 mA output | 1–5 V output |
|---|---|---|---|
| 0% | 0 bar | 4.00 mA | 1.00 V |
| 25% | 2.5 bar | 8.00 mA | 2.00 V |
| 50% | 5 bar | 12.00 mA | 3.00 V |
| 75% | 7.5 bar | 16.00 mA | 4.00 V |
| 100% | 10 bar | 20.00 mA | 5.00 V |
Calibration procedure
- Isolate the transmitter, connect the pressure source and a reference gauge, and connect a multimeter or calibrator in the loop.
- Apply each point upscale (0 → 100%) and record the output, then repeat downscale (100 → 0%).
- Calculate the error at each point as % of span. If any point is out of tolerance, adjust zero and span and repeat to record as-left data.
- For DP flow transmitters with square-root extraction, the output at 25% DP is 50% flow — see the DP flow square-root calculator.
Frequently asked questions
Why calibrate at five points?
Zero and span alone only fix the ends of the range. The 25, 50 and 75% points show non-linearity, and testing upscale then downscale reveals hysteresis.
What are the 5 calibration points for a 4–20 mA transmitter?
4, 8, 12, 16 and 20 mA, corresponding to 0, 25, 50, 75 and 100% of the calibrated input range.
Does the table work for a suppressed or elevated zero?
Yes. Enter a negative LRV for an elevated range (for example −50 to +150 mbar) and the input points are spaced across that range.
What about reverse-acting outputs?
Enter the output high value as the low and vice versa (for example 20 and 4) — the expected outputs then decrease as the input rises.