Signal Converter Calculator (4–20 mA ↔ 0–10 V ↔ 1–5 V)

Field instruments, PLC inputs and drives use different analog standards, and a signal isolator or converter maps one onto another by percent of range. This signal converter calculator translates 4–20 mA, 0–20 mA, 0–10 V and 1–5 V values in any direction — see 4 to 20 mA signal conversion and why 4–20 mA is the best signal for industrial automation.

calculated
calculated
calculated
calculated
calculated
Type in any field to change it. Press × on a value to calculate that field instead.

How to use the signal converter calculator

Enter a value in any one field — a 4–20 mA current, a percent of range or one of the voltage signals — and the calculator fills in the equivalent value for every other standard. All conversions are linear by percent of range.

Signal conversion formulas

% = (I4–20 − 4 mA) ÷ 16 mA

I0–20 = 20 mA × %  ·  V0–10 = 10 V × %  ·  V1–5 = 1 V + 4 V × %  ·  V0–5 = 5 V × %

Example

12 mA on a 4–20 mA loop:

  • Percent = (12 − 4) ÷ 16 = 50%
  • 0–20 mA = 10 mA, 0–10 V = 5 V, 1–5 V = 3 V, 0–5 V = 2.5 V

Signal conversion table

% of range 4–20 mA 0–20 mA 1–5 V 0–10 V
0% 4.00 mA 0.00 mA 1.00 V 0.00 V
10% 5.60 mA 2.00 mA 1.40 V 1.00 V
25% 8.00 mA 5.00 mA 2.00 V 2.50 V
50% 12.00 mA 10.00 mA 3.00 V 5.00 V
75% 16.00 mA 15.00 mA 4.00 V 7.50 V
90% 18.40 mA 18.00 mA 4.60 V 9.00 V
100% 20.00 mA 20.00 mA 5.00 V 10.00 V

Choosing a signal

  • 4–20 mA is immune to voltage drop along the cable, detects a broken wire and can power 2-wire transmitters — the plant standard.
  • 0–10 V is common for drives, dampers and building automation over short distances.
  • 1–5 V is the voltage across a 250 Ω resistor in a 4–20 mA loop and is how many controllers read current inputs.

Frequently asked questions

How do I convert 4–20 mA to 0–10 V?

Find the percent of range, (mA − 4) ÷ 16, then multiply by 10 V. 12 mA is 50%, which is 5 V.

How do I convert 4–20 mA to 1–5 V?

Pass the current through a precision 250 Ω resistor — 4 mA gives 1 V and 20 mA gives 5 V. This is how many DCS and PLC voltage inputs read current loops.

Can I convert 0–10 V to 4–20 mA with a resistor?

No. Converting voltage to a current loop needs an active converter or isolator that drives a controlled current. Going from current to voltage only needs a resistor.

Why is 4 mA used instead of 0 mA?

A live zero lets the receiver tell a 0% signal from a broken wire (0 mA), and leaves enough current to power 2-wire transmitters.