Safe Failure Fraction Calculator (SFF, Diagnostic Coverage)

The safe failure fraction is the share of a device's failures that are either safe or dangerous but detected by diagnostics, and together with hardware fault tolerance it caps the SIL a subsystem can claim. This safe failure fraction calculator works out SFF and diagnostic coverage from the FMEDA failure rates and shows the IEC 61508 architectural limits — background in safe failure fraction in functional safety and hardware fault tolerance and SFF.

FIT
FIT
FIT
FIT
calculated
calculated
90% to below 99%
calculated
years
calculated
Type in any field to change it. Press × on a value to calculate that field instead.

How to use the safe failure fraction calculator

Enter the safe, dangerous detected and dangerous undetected failure rates in FIT from the device’s FMEDA report or safety manual (λS can include λSD + λSU, and λDD includes failures that the diagnostics drive to a safe state). The calculator returns the total failure rate, the SFF with its IEC 61508 band, the diagnostic coverage and the equivalent MTTF.

Safe failure fraction formula

SFF = (λS + λDD) ÷ (λS + λDD + λDU)  ·  DC = λDD ÷ (λDD + λDU)

Worked example

A pressure transmitter with λS = 300 FIT, λDD = 450 FIT and λDU = 50 FIT:

  • Total failure rate = 800 FIT (MTTF ≈ 143 years)
  • SFF = (300 + 450) ÷ 800 = 93.75%
  • DC = 450 ÷ (450 + 50) = 90%
  • As a Type B device with HFT 0 it is limited to SIL 2 (90–99% SFF); in a 1oo2 arrangement (HFT 1) it could be used up to SIL 3

Maximum SIL by SFF and hardware fault tolerance (IEC 61508-2, Route 1H)

SFF Type A, HFT 0 Type A, HFT 1 Type A, HFT 2 Type B, HFT 0 Type B, HFT 1 Type B, HFT 2
< 60% SIL 1 SIL 2 SIL 3 Not allowed SIL 1 SIL 2
60% – < 90% SIL 2 SIL 3 SIL 4 SIL 1 SIL 2 SIL 3
90% – < 99% SIL 3 SIL 4 SIL 4 SIL 2 SIL 3 SIL 4
≥ 99% SIL 3 SIL 4 SIL 4 SIL 3 SIL 4 SIL 4

HFT N means the subsystem still works after N dangerous faults (1oo1 = 0, 1oo2 = 1, 1oo3 = 2).

Practical notes

  • The architectural limit is separate from the PFDavg limit — a SIF must meet both, and the PFDavg depends mainly on λDU and the proof-test interval.
  • IEC 61511 (process sector) allows Route 2H or its own HFT table based on prior use instead of SFF; check which route your project uses.
  • “No effect” and “no part” failures are excluded from the SFF calculation in IEC 61508 Edition 2.
  • Detected failures only count as safe if the diagnostic response actually takes the process to a safe state (or alarms and the repair is done within the MTTR assumed).

Frequently asked questions

How is safe failure fraction calculated?

SFF = (λS + λDD) ÷ (λS + λDD + λDU) — all safe failures plus dangerous detected failures, divided by the total failure rate. Only the dangerous undetected failures count against it.

What SFF is needed for SIL 2?

Under IEC 61508 Route 1H with no redundancy (HFT 0), a Type A device needs SFF ≥ 60% and a Type B device SFF ≥ 90% for SIL 2. With HFT 1, Type A needs no minimum (below 60% is enough) and Type B needs SFF ≥ 60%.

What is the difference between SFF and diagnostic coverage?

Diagnostic coverage looks only at dangerous failures, DC = λDD ÷ (λDD + λDU). SFF also counts safe failures, so a device with many safe failures can have a high SFF even with modest diagnostics.

What are Type A and Type B devices?

Type A devices are simple, with well-known failure modes and field data (relays, solenoid valves, simple transmitters). Type B devices contain complex components such as microprocessors whose failure modes are not fully known — most smart transmitters and logic solvers.